FS#276 — FS # 4360 - RBX 2 UPS 3 battery breaker

Attached to Project— Datacenters
Modernization
New
CLOSED
100%
The UPS 3 RBX 2 has a single breaker that connects to its batteries.
This solution, although it's not a failure in us, has already caused damage in case of failure of the breaker.

As a precaution, we will perform the replacement of the breaker by a single bay
of 3 independent circuit breakers, which will secure the installation.

The operation will take place tomorrow Friday, 09/07 at 08 hours and should last about two hours.
Meanwhile, the UPS will operate with the bypass mode.


Date:  Friday, 09 July 2010, 13:37PM
Reason for closing:  Done
Additional comments about closing:  The replacement was done and the uninterruptible power supply was re-put in rippled mode. All has been done as predicted.

We will do this same operation on other appliances in the next weeks.